| VA / Watt |
Capacity |
8.0KVA / 8000W |
| Input |
Nominal Vottage |
220/230/240 Vac |
Vottage
Range |
Acceptable
Vottage Range |
120Vac-270Vac |
| Frequency |
45Hz - 70Hz Auto Sensing |
| Line Low Transfer |
120Vac ¡Ó 2% |
| Line Low Retum |
130Vac ¡Ó 2% |
| Line High Transfer |
270Vac ¡Ó 2% |
| Line High Retum |
260Vac ¡Ó 2% |
| Output |
Vottage |
220/230/240 Vac
(re-settable
via LCD panel) |
| Voltage Regulation |
Battery Mode:
< 3% RMS for entire battery
voltage range |
Frequency
Regulation |
Line Mode |
Synchronized to AC Main |
| Battery Mode |
50Hz or 60Hz ¡Ó0.1Hz |
| Waveform |
Pure Sine wave |
| Power Factor |
1.0 |
| Effiecincy |
> 80% |
Short Circuit
Protection |
Line Mode |
Circuit Breaker |
| Battery Mode |
Electronic Circuit |
Overload
Protection |
Line Mode |
>110%, Buzzer alarm and Yellow LED blink
continuously. |
| Battery Mode |
110% ~ 150% for 30 sec. , >150% for 200ms,
then UPS shuts down. |
| Transfer Time(Typical) |
< 8 ms. |
| DC Start |
Cold start |
Yes. |
| Battery |
Battery Voltage |
48Vdc |
| Backup Time |
10 ~ 12 hours based on the batteries connected. |
| Recharging current |
Normal 10~20A, 60.0A Max. |
| Control |
LCD Display |
Operation status, I/P&O/P Voltage Frequency,
Load%, Battery Voltage & %, Temperature, Model |
| LED Display |
Normal (Green), Warning (Yellow), Fault (Red) |
| Support solar panel |
Optional function |
Audible
Alarm |
Battery
Mode: Beeping every 4 seconds |
Inverter
Fault: Beeping continuously |
| Low Battery:
Beeping every second |
¡@¡@Overload: Beeping twice
per second |
|
| Parameter Re-settable |
Voltage, Frequency, 5 steps
charge current |
| Environment |
Operation Temperature |
0-40 degree C |
| Relative Humidity |
0-95% non-condensing |
| Audible Noise |
Less than 55dBA (at 1M) |
| Physical |
Wall Mounted Type (W*H*D) |
415*600*260 |
| Wall Mounted Type Net Weight |
53.6 Kgs |
| Safety |
(1) Safety Standard meets EN62040-1-1;
(2) EMC meets EN62040-2;
(3) Marks: CE, cUL , UL |